Description
Download Specification
Description
RCC: circular CAV units
- casing in galvanised steel
- galvanised steel adjustment blades with system to control the oscillations, stainless steel rotation shafts on special bearings
- operating range from 50 to 500 Pa
- velocity working range from 2 to 10 m/s
- operating temperature between -20°C and +70°C
- tolerance ± 10% (up to 100 m3/h: ± 10 m3/h fixed)
- horizontal or vertical assembly
- optional recalibration on worksite
RCC…230: like RCC but with 230V actuator for operation with two flows
RCC…24: like RCC but with 24V actuator for operation with two flows
RCC..I: with insulated casing
Assembly
- Plug-in sound attenuator L = 1000 mm
Assembly:
- install a straight duct section of at least 5xD upstream if connected with hammer release; if connected to rigid duct R min 1.5D